Input | |
---|---|
Sensor supply US | 24 V DC (EN 61131-2), max. 200 mA |
Input range (analog) | 0...10 V |
Valency | 179.4 µV |
Input resistor (analog) | > 100 k? |
Resolution (analog) | 15 Bit + sign |
Accuracy | 0.10% (25 °C) |
Temperature drift | 45 ppm/°K |
Conversion time (analog) | max. 5 ms |
Input filter | yes, mean value formation, parameterizable N = 0...64 |
Invers-polarity protection | yes, permanently |
Over voltage protection | 30 V DC |
Connections | |
IO-Link | M12 (male) 5-pole, A-coded |
Analog input | M12 (female) 5-pole, A-coded, shielded |
Module supply | |
Operating voltage | 24 V DC (18...30 V DC) |
Current consumption | max. 19 mA |
General data | |
Protection | IP65/IP67 |
Material (housing) | Plastic |
Labeling | Laser labelled |
Temperature range | -30...+70 °C (storage temperature -40...+85 °C) |
Dimensions H ? W ? D | 32.3?77.2?15 mm |
IO-Link | |
Specification | IO-Link V1.1 |
Operating modes | COM2 (38.4 kBit/s) |
Port Class | A |
Cycle time | min. 2.3 ms |
Data width | 16 Bit / 2 Byte |
Data format | Siemens S7 |
Parameterization | |
Measured value | preset |
Diagnostics | lower limit, upper limit, over heated, supply over voltage, supply under voltage, defective device, sensor supply over current, overrun |
lower limit | 2 Byte |
upper limit | 2 Byte |
Mean value filter | 1 Byte |
Protection | |
Reverse polarity protection module | yes, permanently |
Short-circuit protection sensor | yes, permanently |
feed back resistance | yes, permanently |
Over voltage protection | 30 V DC |
Diagnostic | |
Communication status | via LED and IO-Link |
Diagnostic via LED | yes |
Diagnostic via IO-Link | yes |
Monitoring - limit | yes |
Monitoring - temperature | yes |
Monitoring - over voltage | yes |
Monitoring - under voltage | yes |
Short-circuit and overload | yes |
Underride and overrun | yes |
Commercial data | |
country of origin | DE |
customs tariff number | 85389099 |
EAN | 4048879622257 |
eClass | 27242601 |
Packaging unit | 1 |